2022-06
Chapter 3

3.3.5 Classes of airtightness

The permissible amount of air leakage is related to classes of airtightness, for which a test pressure applies, which is taken from NEN-EN 1751, NEN-EN 13180 and NEN-EN 15727. Each type of fitting has its own respective standard, which can be found in the legend of the LAR at Luka Fitting Register. Fittings only need to be tested for overpressure.

A report of the measurement, including a graphic representation of the airtightness with respect to the standardised classes must be submitted to the CET for approval via the secretariat. Only fittings that satisfy at least class C can be included in the LAR. An example of such a report/certificate can be found in paragraph 3.3.6.

The minimum number of measuring points and corresponding test pressures for each type of fitting are described in the sections below.

3.3.5.1 Component according to standard NEN-EN 1751 (2014)

Measured at a minimum of three (3) test pressures, namely:

3.3.5.2 Component according to standard NEN-EN 15727 (2010)

Measured at a minimum of three (3) test pressures, namely:

3.3.5.3 Component according to standard NEN-EN 13180 (2002)

Test pressure to be measured is + 1000 Pa.

* A fitting is considered circular if the cross-section (flow area) is circular.
** A fitting whose cross-section (flow area) is rectangular shall remain as such whether or not it is provided with a circular connection(s) for connection to the duct.